Operating Manual Light Control „PULSE HFMD / PULSE PIR - Vers. IV“
ENG
Loading setting level 2
Actuation Display
Light bar LED 1 (dark green)
Parameterisation mode ON
Function 2.2 Automatic switch-on
Light bar LED 2 (light green)
Function 2.2
Changing the function from ON to OFF or vice versa
Setting function 2.2
LED changes from constantly lit
to flashing or vice versa:
- constant = Function ON
- flashing = Function OFF
Press key II once
Loading the parameterisation mode
Light bar LEDs 1+2
Level 2
Automatic switch-on
Function for allowing or suppress-
ing automatic switch-on when
light is insufficient or in case of
presence (semi-automatic).
By default, the function is set to
"ON", i.e., the light is automatically
switched on in case of presence or
when light is insufficient.
When automatic switch-on is off,
the light has to be switched on
manually even in case of pres-
ence.
The function can be changed on
- Lights equipped with HFMD
sensor
- Lights equipped with PIR sensor
Press both keys again
for 5 seconds
Press both keys
for at least 10 seconds
1 x
n x
Press key I as often as
necessary for reaching
the desired value